• Ash container

    Big built in ash container (needs emptying approximately once a month)

  • Draught control

    Integrated flue gas fan working by draught sensor

  • Safety thermostat

    prevents water from exceeding 95 C. Once this occurs, the thermostat must be reset manually.

  • Safety valve

    is applied when pressure in the boiler reaches 2.5 bar

  • Safety door switch

    prevents burner from starting up then door is open. If the door is opened during burining process, the switch triggers burner to stop. Burning process will automatically resume once the door is shut again.

Unit PK100+
Rated thermal outputkW90
Boiler class according to EN 303-55
Minimum returning water temp.°C55
Recommended working temp.°C75
Highest working temp.°C90
Safety thermostat triggering temp.°C95
Permissible operative pressurebar2.5
Test pressurebar 4
Boiler water volumel275
Boiler weightkg495
Boiler dimensions (L/W/H)mm995/785/1700
Intake width without side panelsmm685
Combustion chamber dimensions (L/W/H)mm430/840/710
Combustion air inlet hatchcm²≥600
Mains supply230V, 50Hz
Electrical consumption at ignition *W500
Electrical consumption during work *W70
Electrical consumption at standby *W3
Chimney diametermm≥150
Distance between top connectionsmm560
Flue gas outlet⌀ mm150
Boiler top connections pcs2xG1.5"
Boiler back connectionspcs2xRp1"
Number of turbulatorspcs14
Required safety valve connectionspcs1xDN25
Emissions Unit At nominal power / at minimum power
PowerkW90 / 26
Fluegas temperature at T=75°C148 / 79
Efficiency at T=75°C%92 / 94
CO (10% O2) mg/Nm3216 / 123,7
NOx (10% O2) mg/Nm3150,3 / 124,7
OGC (10% O2) mg/Nm33,8 / 1,5
Dust particles (10% O2) mg/Nm322,1 / 32,6
* Given are electrical consumption with burner corresponding to the boiler