| Unit | PK100+ | |
| Rated thermal output | kW | 90 |
| Boiler class according to EN 303-5 | 5 | |
| Minimum returning water temp. | °C | 55 |
| Recommended working temp. | °C | 75 |
| Highest working temp. | °C | 90 |
| Safety thermostat triggering temp. | °C | 95 |
| Permissible operative pressure | bar | 2.5 |
| Test pressure | bar | 4 |
| Boiler water volume | l | 275 |
| Boiler weight | kg | 495 |
| Boiler dimensions (L/W/H) | mm | 995/785/1700 |
| Intake width without side panels | mm | 685 |
| Combustion chamber dimensions (L/W/H) | mm | 430/840/710 |
| Combustion air inlet hatch | cm² | ≥600 |
| Mains supply | 230V, 50Hz | |
| Electrical consumption at ignition * | W | 500 |
| Electrical consumption during work * | W | 70 |
| Electrical consumption at standby * | W | 3 |
| Chimney diameter | mm | ≥150 |
| Distance between top connections | mm | 560 |
| Flue gas outlet | ⌀ mm | 150 |
| Boiler top connections | pcs | 2xG1.5" |
| Boiler back connections | pcs | 2xRp1" |
| Number of turbulators | pcs | 14 |
| Required safety valve connections | pcs | 1xDN25 |
| Emissions | Unit | At nominal power / at minimum power |
| Power | kW | 90 / 26 |
| Fluegas temperature at T=75 | °C | 148 / 79 |
| Efficiency at T=75°C | % | 92 / 94 |
| CO (10% O2) | mg/Nm3 | 216 / 123,7 |
| NOx (10% O2) | mg/Nm3 | 150,3 / 124,7 |
| OGC (10% O2) | mg/Nm3 | 3,8 / 1,5 |
| Dust particles (10% O2) | mg/Nm3 | 22,1 / 32,6 |